SPECIFICATIONS :
1. ELECTRICAL :
a. Working Voltage : 90 to 220 V AC, 1Æ, 50Hz


b. Sensor Input : All types of T/C, RTD, PT 100, mV or mA, Bridge sensors like strain gauge, load cells etc. In-built cold junction compensation.

c. Control parameters. All parameters are keyboard programmable.
1. Setpoint adjustable 0 to 100% of SPAN
2. Proportional Band : 0 to 100% of span. If set to 0% the controller is ON/OFF controller.
3. Integral Time (Reset) : 0 to 3600 Sec.
4. Rate (Derivative) : 0 to 1000 Sec.
5. Dead Band (ON/OFF control hysteresis) : 0 to 20% span.
6. Inhibit reset : The integral action is suspended outside proportional band.
7. Time proportional action : Can be set up to 99 Seconds.
8. Soft Start : 0 to 60 unit / minute.

d. Display : 4 digit 7 segment 0.5" for process value pV and 4 digit 7 segment 0.5" display for set value sV for model 5150 MD. 7 segment 0.3" display for set point and process value for 5150M. LED display for Alarms and outputs. Scaling of the display and resolution is user programmable.

e. Controlling Ouput : 3 options are available which should be specified by the user. 1. Relay : 3A, 240V AC max for resistive load. 2. 4 to 20mA max. load 12V with built in power supply. 3. 0 to 10V.

f. Alarms : Two alarms points can be set from 0 to 100% of the span with 0 to 20% hysteresis. The alarm output can be: 1. Relay : 1 C/O 240V AC, 3A max. 2. Level : 5V DC logic signal.

g. Soak : One alarm output can be programmed as soak timer from 0 to 3600 minutes. The corresponding relay can be energised during soak period.

h. Re transmission : 4 to 20mA or serial communication RS485 / RS232 is available. The scaling is as per the user programme.

i. Serial Communication : 2 wire multidrop, half duplex, asynchronous polled, 9600 baud rate, Max. No. of Controllers on single loop 31, RS 485 protocol. The computer requires RS 485 port or RS232C / RS485 convertor. Driver software is available at extra cost. The driver software is DOS/WINDOWS based.

j. Accuracy :

  Sensor Range Accuracy
1. RTD PT 100 -200° to +500°C +/- 2°C
2. T/C J Type -50° to 1000°C +/- 2°C
3. T/C K Type -50° to 1370°C +/- 2°C
4. T/C R Type 0° to +1350°C +/- 2°C
5. T/C S Type 0° to +1350°C +/- 2°C
6. T/C T Type -27° to 400°C +/- 2°C
7. Linear mV - 100 to +100mV +/- 0.5% of range
8. Linear Current 4 to 20 mA +/- 0.5% of range
9. Volts DC 0 to 10V +/- 0.5% of range

Note : Specifications g, h, i are options and are not included in normal model. These options should be specified at the time of the order. These will be charged separately.

2. MECHANICAL :
Size : 96 x 96 x 200 mm for DIN model and 4U height and 10T width and 200mm depth for modular version. 8 such modules can be accmmodatd in standard 19" rack. The total system consists of 8 such zones in upper half and SSR (solid state relays) in the bottom half.

3. ENVIRONMENTAL :
a. Working temperature range : 5° to 50°C at 90% R.H. non-condensing.
b. Storage temperature range : 0° to 60°C at 95% R.H.

<<BACK